Public preview. Built from real public data on November 9, 2026, 5:41 AM UTC.
Securidigm Watch Transportation cyber intel
Home / Items
Vendor advisorySeverity 7.5 high

AC500 V3 - Invalid type usage in visualization

3ADR011565 · ABB · September 28, 2026

Summary

An update is available that resolves publicly reported vulnerability in the products versions listed as affected in the advisory. An attacker who successfully exploited these vulnerabilities could cause a denial-of-service (DoS).

From ABB (vendor's own words, quoted), quoted as published. Check the source before acting.

What to do

The problem is corrected in the following product version: - AC500 V3 firmware version 3.9.1 ABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and integrated into Automation Builder 2.9.1. Automation Builder 2.9.1 is available for download from the related download site. https://www.abb.com/global/en/areas/motion/digital-tools/automation-builder/software-download Refer to section “General security recommendations” for further advise on how to keep your system secure. Disable the web server, if it is enabled, but not required for the PLC operation.

Vendor fix or mitigation, quoted from the advisory.

Each CVE in this advisory

CVESeverityKnown exploitedExploit likelihoodWeakness
CVE-2025-417387.5 highNo0.4%Access of Resource Using Incompatible Type (CWE-843)

Severity from the advisory (CVSS), known exploitation from CISA's catalog, exploit likelihood from EPSS (next 30 days).

Affected products

VendorProductAffected versionsFixed
ABBAC500 V3 PM5xxx——
ABBAC500 V3 Firmware——

Why it's on these mode pages

  • Pipeline: Vendor table: ABB (matched by rule)

Change history

  1. September 28, 2026: Initial version.
  2. November 9, 2026: First collected by Watch

Securidigm Scout can match advisories like this one to the equipment on your own network, offline. securidigm.com