Industrial control advisorySeverity 8.3 high
Schneider Electric Easergy, EcoStruxture, PowerLogic, and Saitel Products (Update A)
ICSA-26-169-07 · CISA · May 12, 2026
Summary
Schneider Electric is aware of a vulnerability in the following products:
The Easergy C5 is a scalable and interoperable bay controller, protection and merging unit for large and critical
infrastructure electrical distribution systems.
The Easergy MiCOM P30 is a family of multifunction protection and control relays designed for medium, high
and extra high voltage electrical networks.
The Easergy MiCOM P40 is a protection relay series for Medium Voltage, High Voltage and Extra High Voltage
protection.
The Easergy MiCOM C264 is a modular and compact substation or bay controller, smart RTU and MV one box
solution
The EcoStruxure™ Power Automation System Gateway (EPAS=GTW) is a scalable, interoperable, and
rugged communication gateway that helps to remotely monitor and operate electrical processes
The EcoStruxure Power Automation System User Interface (EPAS-UI) product is an HMI SCADA designed for
electrical networks and substations operations.
The EcoStruxure Power Automation System Intelligent Power Management System and Fast Load Shedding
(iPMFLS) is a range of solutions designed to overcome size and performances constraints.
The EcoStruxure™ Power Operation (EPO) are an on-premises software offers that provides a single platform
to monitor and control medium and lower power systems.
The PowerLogic™ P5 is a medium voltage protection relay.
The PowerLogic™ P7 is a protection and control platform designed for complex and advanced electrical
network applications.
The PowerLogic™ T300 is a modular platform for medium voltage and low voltage public distribution network
management.
The PowerLogicTM T500 is a control unit and RTU for substation automation.
The Saitel DP RTU is a modular platform for medium voltage and low voltage public distribution and
transmission network management.
The EasyLogic T150 (formerly Saitel DR RTU) is a field device, offering a solid and powerful platform for data
acquisition, communication, automation and IED integration for distribution and transmission networks,
generation sector and railway.
Failure to apply the fix provided below may risk session hijacking, which could result in malicious actors
performing unauthorized operations within the affected system.
From CISA, quoted as published. Check the source before acting.
What to do
Version D7.34 of MiCOM C264 includes a fix for this vulnerability. Contact
Schneider Electric’s Customer Care Center for information on how to
contact your local Application Center to update the device.
Reboot is required
Version 1.1.18 of Easergy C5 includes a fix for this vulnerability.
Contact Schneider Electric’s Customer Care Center for information on how
to contact your local Application Center to update the device.
Reboot is required
Version P139.678.700 Easergy MiCOM P139 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
Version P439.678.700 Easergy MiCOM P439 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
Version P539.678.700 Easergy MiCOM P539 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
Version P632.678.700 Easergy MiCOM P632 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
Version P633.678.700 Easergy MiCOM P633 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
Version P634.680.701 Easergy MiCOM P634 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
Version P633.680.701 Easergy MiCOM P633 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
Version P138.677.701 Easergy MiCOM P138 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
Version C434.679.700 Easergy MiCOM C434 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.
HUe Firmware version 11.06.31 includes a fix for this
vulnerability and is available for download here:
. Contact Schneider Electric’s Customer Care Center to download this software.
A reboot is needed to complete the firmware upgrade
Version 6.4.610.500.101 of EPAS Gateway includes a fix for this
vulnerability. Contact Schneider Electric’s Customer Care Center to
download this software
Version 3.0.4 of EPAS-UI includes a fix for this vulnerability. Contact
Schneider Electric’s Customer Care Center to download this software.
EPO 2022 CU 7 of EcoStruxure™ Power Operation includes a fix for this
vulnerability and is available for download here:
• https://community.se.com/t5/EcoStruxure-PowerOperation/Power-Operation-2022-CU7-is-Now-Available/tdp/524787
Reboot needed: yes
EPO 2024 CU 3 of EcoStruxure™ Power Operation includes a fix for this
vulnerability and is available for download here:
• https://community.se.com/t5/EcoStruxure-PowerOperation/Power-Operation-2024-CU3-is-HERE/td-p/534769
Reboot needed: yes
Version 64.2025.0.14 of iPMFLS includes a fix for this vulnerability. Contact
Schneider Electric’s Customer Care Center for information on how to
contact your local Application Center to update the device.
Version V02.503.101 of PowerLogic™ P5 includes a fix for this vulnerability
Contact Schneider Electric’s Customer Care Center to download this
firmware.
Version V02.003.001 of PowerLogic™ P7 includes a fix for this vulnerability
Contact Schneider Electric’s Customer Care Center to download this
firmware.
Version 2.9.5 of PowerLogic™ T300 includes a fix for this vulnerability
Contact Schneider Electric’s Customer Care Center to download this
firmware.
A reboot is needed to complete the firmware upgrade
Version 11.08.03 of PowerLogic™ T500 includes a fix for this vulnerability
Contact Schneider Electric’s Customer Care Center to download this
firmware.
A reboot is needed to complete the firmware upgrade
CPU866e Firmware version 11.06.37 includes a fix for this
vulnerability and is available for download. Contact Schneider Electric’s Customer Care Center to download this firmware.
A reboot is needed to complete the firmware upgrade
Schneider Electric is establishing a remediation plan for all future versions
of the following models of the Easergy MiCOM P30:
P437
P532
P631
P634
P436
P438
P638
Future versions will include a fix for this vulnerability. We will update this
document when the remediation is available.
Until then, customers should immediately apply the following mitigations to
reduce the risk of exploit:
• Ensure P30 operates within a physically or logically segmented
internal network. Access to this network should be tightly controlled
using standard security mechanisms such as firewalls, intrusion
detection systems (IDS), and other relevant protective measures.
• Reduce the “Minimum inactivity period” using the CAE tool to
shorten session timeout durations and minimize the risk of
unauthorized access due to inactive sessions
Schneider Electric is establishing a remediation plan for a future version of
the Easergy MiCOM P40 Series model numbers with Protocol Option bit as
G, H or L.
P_ 4_ _ _ _ _ G_ _ _ _ _ M
P_ 4_ _ _ _ _ H_ _ _ _ _ M
P_ 4_ _ _ _ _ L _ _ _ _ _ M
P_ 4_ _ _ _ _ G_ _ _ _ _ L
P_ 4_ _ _ _ _ H_ _ _ _ _ L
P_ 4_ _ _ _ _ L _ _ _ _ _ L
A future version will include a fix for this vulnerability. We will update this
document when the remediation is available.
Until then, customers should immediately apply the following mitigations to
reduce the risk of exploit:
• Ensure P40 operates within a physically or logically segmented
internal network. Access to this network should be tightly controlled
using standard security mechanisms such as firewalls, intrusion
detection systems (IDS), and other relevant protective measures.
• Reduce the “Minimum inactivity period” using the CAE tool to
shorten session timeout durations and minimize the risk of
unauthorized access due to inactive sessions
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.
Vendor fix or mitigation, quoted from the advisory.
Each CVE in this advisory
| CVE | Severity | Known exploited | Exploit likelihood |
|---|---|---|---|
| CVE-2026-4827 | 8.3 high | No | 0.3% |
Severity from the advisory (CVSS), known exploitation from CISA's catalog, exploit likelihood from EPSS (next 30 days).
Affected products
| Vendor | Product |
|---|---|
| Schneider Electric | Easergy MiCOM C264 |
| Schneider Electric | Easergy MiCOM P139 |
| Schneider Electric | Easergy MiCOM P437 |
| Schneider Electric | Easergy MiCOM P439 |
| Schneider Electric | Easergy MiCOM P532 |
| Schneider Electric | Easergy MiCOM P539 |
| Schneider Electric | Easergy MiCOM P631 |
| Schneider Electric | Easergy MiCOM P632 |
| Schneider Electric | Easergy MiCOM P633 |
| Schneider Electric | Easergy MiCOM P634 |
| Schneider Electric | Easergy MiCOM P138 |
| Schneider Electric | Easergy MiCOM P436 |
| Schneider Electric | Easergy MiCOM P438 |
| Schneider Electric | Easergy MiCOM P638 |
| Schneider Electric | Easergy MiCOM C434 |
| Schneider Electric | EcoStruxure Power Automation System Gateway (EPAS-GTW) |
| Schneider Electric | EcoStruxure Power Automation System User Interface (EPAS-UI) |
| Schneider Electric | EcoStruxure Power Operation |
| Schneider Electric | iPMFLS |
| Schneider Electric | PowerLogic P5 Protection Relay |
| Schneider Electric | PowerLogic P7 Protection and Control Platform |
| Schneider Electric | PowerLogic T300 |
| Schneider Electric | PowerLogic T500 |
| Schneider Electric | Saitel DP |
| Schneider Electric | EasyLogic T150 (formerly Saitel DR) |
| Schneider Electric | Easergy C5 |
| Schneider Electric | Easergy MiCOM P139 version |
| Schneider Electric | Saitel DR |
| Schneider Electric | EcoStruxure Power Automation Automation System User Interface (EPAS-UI) |
| Schneider Electric | EcoStruxure Power Operation (EPO) |
| Schneider Electric | Easergy MiCOM P40 Series |
Why it's on these mode pages
- Pipeline: Vendor table: Schneider Electric (matched by rule)
Change history
- May 12, 2026: Original Release
- June 18, 2026: CISA Republication - Initial CISA Republication of Schneider Electric CPCERT SEVD-2026-132-02 advisory
- August 25, 2026: Removed PowerChute Serial Shutdown as the product is not part of the Security Notification.
- September 3, 2026: CISA Republication update based on Schneider Electric CPCERT SEVD-2026-132-02 advisory
- November 9, 2026: First collected by Watch
Securidigm Scout can match advisories like this one to the equipment on your own network, offline. securidigm.com