Industrial control advisorySeverity 7.1 high

AVEVA Enterprise SCADA

ICSA-26-225-01 · CISA · August 13, 2026

Summary

Successful exploitation of this vulnerability could allow an attacker to tamper with serialized data, potentially resulting in code execution during deserialization.

From CISA, quoted as published. Check the source before acting.

What to do

AVEVA recommends that customers using affected product versions should perform the following to mitigate the risk of exploit: 1. Evaluate the impact of these vulnerabilities based on your operational environment, architecture, and product implementation. 2. Plan an upgrade of Servers and Clients to one of the available fixed versions listed in this document. 3. Configure Servers and Clients as described in this document. Contact your AVEVA Technical Support representative, Customer Success Manager, Account Manager, or Solution Integrator to obtain the security update best applicable to the product version currently deployed in your environment: Servers: AVEVA Enterprise SCADA v2025 P1 or higher, AVEVA Enterprise SCADA v2024 SP1 P2, AVEVA Enterprise SCADA v2023 SP1 P1, AVEVA Enterprise SCADA v2022 SP2 P3, AVEVA Enterprise SCADA v2021 SP2 P6, AVEVA Pipeline Operations for Gas/Liquids v2025 P1 or higher, AVEVA Pipeline Operations for Gas/Liquids v2024 SP1 P2, AVEVA Pipeline Operations for Gas/Liquids v2023 SP1 P1, AVEVA Pipeline Operations for Gas/Liquids v2022 SP2 P3, AVEVA Pipeline Operations for Gas/Liquids v2021 SP2 P6 Clients: AVEVA Enterprise SCADA HMI v2024 R2 HF7 or higher, AVEVA Enterprise SCADA HMI v2024 P1, AVEVA Enterprise SCADA HMI v2023 P2 HF1, AVEVA Pipeline Integrity Monitor (delivered on Pipeline Simulation media) v2025 SP1 P2 or higher, AVEVA Pipeline Training Simulator (delivered on Pipeline Simulation media) v2025 SP1 P2 or higher, Measurement Advisor 2025 P1 or higher, Measurement Advisor 2021 SP1 HF16 To fully mitigate the risk of exploit, the following configuration changes must be implemented after all server and client nodes have been upgraded to compatible versions that support the fix:Server Components: Change "BinarySerializer" -> "Mode" setting from 'Binary Formatter' to 'Json'. Change "BinarySerializer" -> "AcceptBinaryFormattedData" setting from 'true' to 'false'. Re-cache the XOS Event Handlers assembly Client Components: Configure clients/products that interface with Enterprise SCADA to only use JSON serialization. HMI: Migrate HMI displays For step-by-step instructions on where and how to apply these configuration settings, how to migrate HMI displays, compatible server-client versions list, and additional details please refer to KB117814 "AVEVA Midstream Product Bulletin - Removal of Binary Formatter" AVEVA recommends the following general defensive measures: Audit devices, network topology, and perimeter defences to ensure all applicable security best practices from AVEVA's Enterprise SCADA Reference System Architecture are adhered to. Audit assigned permissions to ensure that only trusted users are given "DNA Authority - Operator" rights: https://docs.aveva.com/bundle/scada-ent-2025/page/651008.html Disallow BLT Test clients in production environmentsFor additional details on defensive measures, refer to Section 5 of KB117814 "AVEVA Midstream Product Bulletin - Removal of Binary Formatter For more information on this vulnerability, including security updates, users should see the security bulletin AVEVA-2026-005.

Vendor fix or mitigation, quoted from the advisory.

Each CVE in this advisory

CVESeverityKnown exploitedExploit likelihoodWeakness
CVE-2025-76397.1 highNo0.6%Deserialization of Untrusted Data (CWE-502)

Severity from the advisory (CVSS), known exploitation from CISA's catalog, exploit likelihood from EPSS (next 30 days).

Affected products

VendorProductAffected versionsFixed
AVEVAEnterprise SCADA2025, >=2024|<=2024_SP1_P01, >=2023|<=2023_SP1, >=2022|<=2022_SP2_P2, <=2021_SP2_P5—
AVEVAEnterprise SCADA HMI2024|2024|R2, <=2023_P1—

Why it's on these mode pages

  • Pipeline: Vendor table: AVEVA (matched by rule)

Change history

  1. August 13, 2026: Initial Republication of AVEVA security bulletin AVEVA-2026-005