Summary

Schneider Electric is aware of a vulnerability in its Modicon M340 https://www.se.com/ww/en/product-range/1468-modicon-m340-pac/, BMXNOR0200H https://www.se.com/us/en/product/BMXNOR0200H/communication-module-modicon-m340-iec-608705101-104-dnp3-for-severe-environments/: Modicon M340 X80 Ethernet Communication Modules, BMXNGD0100 https://www.se.com/us/en/product/BMXNGD0100/communication-module-modicon-m580-global-data-service/: M580 Global Data module, BMXNOC0401 https://www.se.com/us/en/product/BMXNOC0401/network-module-modicon-m340-ethernet-ip-and-modbus-tcp-4-x-rj45/?pageType=product&sourceId=BMXNOC0401: Modicon M340 X80 Ethernet Communication modules, BMXNOE0100 https://www.se.com/ww/en/product/BMXNOE0100/network-module-modicon-m340-modbus-tcp-1-x-rj45-flash-memory-card/?pageType=product&sourceId=BMXNOE0100: Modbus/TCP Ethernet Modicon M340 module, BMXNOE0110 https://www.se.com/ww/en/product/BMXNOE0110/ethernet-tcp-ip-network-module-modicon-m340-automation-platform-flash-memory-card-internal-ram-16-mb-1-x-rj45-10-100/: Modbus/TCP Ethernet Modicon M340 FactoryCast module product(s). Failure to apply the fix provided below may risk Denial Of Service attack, which could result in the unavailability of the devices.

From CISA, quoted as published. Check the source before acting.

What to do

Version 3.60 of BMXNOE0100 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product/BMXNOE0100/networkmodule-modicon-m340-modbus-tcp-1-x-rj45-flash-memorycard/ Reboot is needed to complete the firmware upgrade Version 6.80 of BMXNOE0110 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product/BMXNOE0110/ethernettcp-ip-network-module-modicon-m340-automation-platformflash-memory-card-internal-ram-16-mb-1-x-rj45-10-100/ Reboot is needed to complete the firmware upgrade Version SV3.70 of Modicon M340 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/1468-modicon-m340/#software-and-firmware Version SV1.7 IR27 of BMXNOR0200H includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product/BMXNOR0200H/ethernet-serial-rtu-module-2-x-rj45/ If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • FTP service is disabled by default • Ensure to disable FTP service when not in use • Setup network segmentation and implement a firewall to block all unauthorized access to ports 21/FTP • Use VPN (Virtual Private Networks) tunnels if remote access is required Schneider Electric is establishing a remediation plan for all future versions of • Modicon M340 • BMXNOR0200H • BMXNGD0100 • BMXNOC401 We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • FTP service is disabled by default • Ensure to disable FTP service when not in use • Setup network segmentation and implement a firewall to block all unauthorized access to ports 21/FTP • Use VPN (Virtual Private Networks) tunnels if remote access is required

Vendor fix or mitigation, quoted from the advisory.

Each CVE in this advisory

CVESeverityKnown exploitedExploit likelihoodWeakness
CVE-2025-66257.5 highNo0.5%Improper Input Validation (CWE-20)

Severity from the advisory (CVSS), known exploitation from CISA's catalog, exploit likelihood from EPSS (next 30 days).

Affected products

VendorProductAffected versionsFixed
Schneider ElectricModicon M340 Firmware——
Schneider ElectricModicon M340 Controller——
Schneider ElectricEthernet / Serial RTU Modulevers:generic/<SV1.7_IR27SV1.7_IR27
Schneider ElectricM580 Global Data modulevers:all/*—
Schneider ElectricModicon M340 X80 Ethernet Communication modulesvers:all/*—
Schneider ElectricModbus/TCP Ethernet Modicon M340 modulevers:intdot/<3.603.60
Schneider ElectricModbus/TCP Ethernet Modicon M340 FactoryCast modulevers:intdot/<6.806.80

Why it's on these mode pages

  • Pipeline: Vendor table: Schneider Electric (matched by rule)

Change history

  1. August 12, 2025: Original Release
  2. April 14, 2026: Remediation is available for Modicon M340
  3. August 11, 2026: Remediation is available for BMXNOR0200H.
  4. September 17, 2026: Initial CISA Republication of Schneider Electric CPCERT SEVD-2025-224-05 advisory
  5. November 9, 2026: First collected by Watch