Home / Items
Industrial control advisorySeverity 7.5 high
Schneider Electric Modicon M340 Controller and Communication Modules
ICSA-26-260-04 · CISA · August 12, 2025
Summary
Schneider Electric is aware of a vulnerability in its Modicon M340 https://www.se.com/ww/en/product-range/1468-modicon-m340-pac/, BMXNOR0200H https://www.se.com/us/en/product/BMXNOR0200H/communication-module-modicon-m340-iec-608705101-104-dnp3-for-severe-environments/: Modicon M340 X80
Ethernet Communication Modules, BMXNGD0100 https://www.se.com/us/en/product/BMXNGD0100/communication-module-modicon-m580-global-data-service/: M580 Global Data module, BMXNOC0401 https://www.se.com/us/en/product/BMXNOC0401/network-module-modicon-m340-ethernet-ip-and-modbus-tcp-4-x-rj45/?pageType=product&sourceId=BMXNOC0401: Modicon M340
X80 Ethernet Communication modules, BMXNOE0100 https://www.se.com/ww/en/product/BMXNOE0100/network-module-modicon-m340-modbus-tcp-1-x-rj45-flash-memory-card/?pageType=product&sourceId=BMXNOE0100: Modbus/TCP Ethernet Modicon M340 module,
BMXNOE0110 https://www.se.com/ww/en/product/BMXNOE0110/ethernet-tcp-ip-network-module-modicon-m340-automation-platform-flash-memory-card-internal-ram-16-mb-1-x-rj45-10-100/: Modbus/TCP Ethernet Modicon M340 FactoryCast module product(s).
Failure to apply the fix provided below may risk Denial Of Service attack, which could result in the unavailability
of the devices.
From CISA, quoted as published. Check the source before acting.
What to do
Version 3.60 of BMXNOE0100 includes a fix for this
vulnerability and is available for download here:
https://www.se.com/ww/en/product/BMXNOE0100/networkmodule-modicon-m340-modbus-tcp-1-x-rj45-flash-memorycard/
Reboot is needed to complete the firmware upgrade
Version 6.80 of BMXNOE0110 includes a fix for this
vulnerability and is available for download here:
https://www.se.com/ww/en/product/BMXNOE0110/ethernettcp-ip-network-module-modicon-m340-automation-platformflash-memory-card-internal-ram-16-mb-1-x-rj45-10-100/
Reboot is needed to complete the firmware upgrade
Version SV3.70 of Modicon M340 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/1468-modicon-m340/#software-and-firmware
Version SV1.7 IR27 of BMXNOR0200H includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product/BMXNOR0200H/ethernet-serial-rtu-module-2-x-rj45/
If customers choose not to apply the remediation provided above, they should immediately apply the following
mitigations to reduce the risk of exploit:
• FTP service is disabled by default
• Ensure to disable FTP service when not in use
• Setup network segmentation and implement a
firewall to block all unauthorized access to ports
21/FTP
• Use VPN (Virtual Private Networks) tunnels if
remote access is required
Schneider Electric is establishing a remediation plan for all
future versions of
• Modicon M340
• BMXNOR0200H
• BMXNGD0100
• BMXNOC401
We will update this document when the remediation is
available. Until then, customers should immediately apply
the following mitigations to reduce the risk of exploit:
• FTP service is disabled by default
• Ensure to disable FTP service when not in use
• Setup network segmentation and implement a
firewall to block all unauthorized access to ports
21/FTP
• Use VPN (Virtual Private Networks) tunnels if
remote access is required
Vendor fix or mitigation, quoted from the advisory.
Each CVE in this advisory
| CVE | Severity | Known exploited | Exploit likelihood |
|---|---|---|---|
| CVE-2025-6625 | 7.5 high | No | 0.5% |
Severity from the advisory (CVSS), known exploitation from CISA's catalog, exploit likelihood from EPSS (next 30 days).
Affected products
| Vendor | Product |
|---|---|
| Schneider Electric | Modicon M340 Firmware |
| Schneider Electric | Modicon M340 Controller |
| Schneider Electric | Ethernet / Serial RTU Module |
| Schneider Electric | M580 Global Data module |
| Schneider Electric | Modicon M340 X80 Ethernet Communication modules |
| Schneider Electric | Modbus/TCP Ethernet Modicon M340 module |
| Schneider Electric | Modbus/TCP Ethernet Modicon M340 FactoryCast module |
Why it's on these mode pages
- Pipeline: Vendor table: Schneider Electric (matched by rule)
Change history
- August 12, 2025: Original Release
- April 14, 2026: Remediation is available for Modicon M340
- August 11, 2026: Remediation is available for BMXNOR0200H.
- September 17, 2026: Initial CISA Republication of Schneider Electric CPCERT SEVD-2025-224-05 advisory
- November 9, 2026: First collected by Watch
Securidigm Scout can match advisories like this one to the equipment on your own network, offline. securidigm.com